Technical
Specification And Data
Voltage:
415V
Switching Duty: AC-23 Continuous duty
Current Rating: 32A to
400A
Frequency: 50-60 Hz
No. of Poles: 4 pole(3 pole & 2 pole on request)
| Current
Rating |
AMPS |
32 |
63 |
100 |
125 |
200 |
250 |
315 |
400 |
Rated Current at 415 V 50 Hz
In free air
In enclosure
In enclosure with Solid
link |
AMPS
AMPS
AMPS
|
40
40
50 |
75
63
75 |
125
100
125 |
125
112
125 |
225
200
250 |
300
250
300 |
330
315
330 |
450
400
450 |
|
Rated insulation
voltage |
Volts |
660 |
660 |
660 |
660 |
660 |
660 |
660 |
660 |
Rated fused short circuit current
in:
closed or making condition or RMS - 415 V |
KA |
50 |
50 |
80 |
80 |
100 |
100 |
100 |
100 |
Rated short time
withstand
Current (1 sec RMS 415 V) |
KA
|
2 |
2 |
5 |
5 |
8 |
8 |
10 |
10 |
|
Rated
Operational power
AC 23 at 415V |
KW |
15 |
30 |
60 |
60 |
90 |
132 |
160 |
200 |
|
Rated
breaking capacity
AC
23, COS = 0.35 |
AMPS
|
500 |
500 |
800 |
800 |
3200 |
3200 |
3200 |
3200 |
|
Mechanical
Endurance |
Oper. |
10,000 |
10,000 |
5000 |
5000 |
3000 |
3000 |
3000 |
3000 |
|
Maximum Cable accomodated |
MM2 |
10 |
25 |
70 |
70 |
185 |
240 |
240 |
240 |
Weight of Free standing switch
Open
execution
With
Enclosure |
KG
KG
|
6.5
20
|
6.5
20
|
6.8
20.3
|
7
20.5
|
28.5
46.8
|
29.5
46.8 |
30.5
48.8
|
40
58.3
|
HRC fuse link accepted
Bolted (type
NIT)
Knife (type KD) |
BS
DIN
|
KIA
KD00
|
KIA/KIS
KD00
|
KIS/KCP
KD00
|
KCP/KFP
KD00
|
KC/KTF
KD1
|
KKF/KTF/KC
KD1 |
KKF/KTF
KD2
|
KKF/KTS
KD2
|
|