POWER LOSS
The table below gives the power loss of the device in watts for each rating per pole for the rated current

Rated
Current A
0.5 1 2 3 4 5 6 10 16 20 25 32 40 50 63
KEW MCB 1.36 1.55 1.66 1.98 1.96 1.78 1.91 1.4 2.05 2.2 2.31 3.28 3.52 4.5 5.56
* as per IEC 898 3 3 3 3 3 3 3 3.5 3.5 4.5 4.5 6 7.5 9 13

* Max. allowable Watt lose per pole

TECHNICAL DATA

SPECIFICATION                 : IS 8828(1996) IEC 898- 1995
NO. OF POLES                   : SP, DP, TP, FP, SPN & TPN
RATED CURRENT                : 0.5 A - 63 A
RATED VOLTAGE                : 240 / 415 VAC & 220VDC
RATED BREAKING               : 10000 A (as per IS 8828 at 
CAPACITY                           : 240 / 415V)
RATED FREQUENCY            : 50 / 60 HZ
TRIPPING CHARACTERISTIC : B & C
INSULATION VOLTAGE        : 500V
IMPULSE WITH STAND 
VOLTAGE                            : 5 KV (1.2/50 us)
DEGREE OF PROTECTION   : IP 20
MOUNTING                         : CLIP ON DIN RAIL 35 mm
AMBIENT TEMPERATURE     : -50C to +550C
TERMINAL CAPACITY          : 1 - 25 mm2

NOTE :-0.5A to 5A available in C curve characteristic only.